General specifications | |
---|---|
Signal type | Analog input |
Supply | |
Rated voltage | 12 ... 35 V DC loop powered |
Power dissipation | 0.4 W |
Input | |
Connection side | field side |
Connection | terminals 1+, 2-, 3- thermocouples type E, J, K, N, R, S or T cold junction referenced to 0 °C (32 °F) |
Lead resistance | max. 100 ? per line |
Current | lead monitoring ON: ? 15 nA; OFF: ? 1 nA |
Output | |
Connection side | control side |
Connection | terminals 9+, 8- |
Load | (U -12 V) / 0.02 A |
Current output | 4 ... 20 mA , limited to ? 35 mA |
Fault signal | downscaling ? 3 mA , upscaling ? 22 mA |
Transfer characteristics | |
Measurement range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable |
Deviation | |
Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) |
Rise time | 250 ms |
Galvanic isolation | |
Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 Veff |
Indicators/settings | |
Control elements | DIP-switch rotary switch |
Configuration | via DIP switches via rotary switch |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Insulation coordination | EN 50178 |
Galvanic isolation | EN 50178 |
Degree of protection | IEC 60529 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |